Sulphuric Acid Fume Scrubbing for Autosmart’s Burntwood Production Line
Project Overview
ERG Air Pollution Control supplied a packed tower scrubber for APS on behalf of Autosmart at its Burntwood site. Delivered in 2024, the package was supplied to treat fumes collected by local exhaust ventilation (LEV) from a new automotive cleaning products line.
The case sheet records a gas flow rate of 4,600 m³/h and a stated sulphuric acid removal efficiency of 98%. The package included a uPVC/GRP packed tower scrubber and discharge stack, a GRP fan, a polypropylene magnetic-drive recirculation pump and a control panel.
The Challenge – Treating Acid Fumes from a New Production Line
Local exhaust ventilation captures fumes near the point where they are released and carries them away from the production area. The scrubber then treats the collected air before discharge. These are separate duties, and the treatment package must accommodate the airflow delivered by the extraction system.
For Autosmart, sulphuric acid was the documented treatment target. Equipment handling an acidic air stream and scrubbing liquor needs materials suited to the chemical exposure. That applies to the scrubber vessel as well as the liquid-handling equipment, fan and discharge connections.
ERG’s Solution – Packed Tower Wet Scrubbing
ERG supplied a packed tower scrubber to bring the extracted air into contact with a scrubbing liquid. Inside the tower, liquid is distributed over a bed of packing. The packing creates a large wetted surface, increasing the area available for contact as air passes through the vessel.
The effectiveness of wet scrubbing depends on how the acid is carried in the extracted air, how evenly air and liquid are distributed, and the conditions maintained in the liquid circuit. The case sheet gives a stated removal efficiency of 98% for sulphuric acid for the Autosmart system.
The recirculation pump returns liquid to the tower’s distribution system so the packing stays wetted during operation. A magnetic-drive pump transmits power to the impeller through a magnetic coupling, avoiding the need for a rotating shaft seal where the drive meets the pumped liquid.
Engineering and System Integration
The scrubber and discharge stack were specified in unplasticised polyvinyl chloride and glass-reinforced plastic (uPVC/GRP). The fan was specified in GRP, and the recirculation pump in polypropylene. These material choices show how the package specification extended across both the air path and the liquid circuit.
The fan provides the pressure needed to move air through the treatment equipment and onward to the stack. When selecting a fan for a system like this, the resistance of the packing, ductwork and connections needs to be considered alongside the required airflow. The control panel formed part of ERG’s supply, bringing the electrical controls into the same equipment package.
Project Technical Specifications
Parameter | Project details |
Client | APS |
End user | Autosmart |
Site | Burntwood |
Application | Fume treatment for a new automotive cleaning products line |
Air source | Local exhaust ventilation extracts |
Target contaminant | Sulphuric acid |
Stated gas flow rate | 4,600 m³/h |
Stated sulphuric acid removal efficiency | 98% |
Scrubber | uPVC/GRP packed tower |
Scrubber design reference | Generally in accordance with BS EN 13121-3, as described in the case sheet |
Fan | GRP |
Recirculation pump | Polypropylene magnetic-drive pump |
Discharge stack | uPVC/GRP |
Controls | Control panel |
Year delivered | 2024 |
Engineering Benefits
- Treatment for captured production fumes. The packed tower provided wet scrubbing for the sulphuric acid duty from the new line’s LEV extracts.
- Materials specified across the package. The equipment specification covered the tower, stack, fan and recirculation pump.
- Air handling, liquid circulation and controls included. The supporting equipment formed part of the same supply as the scrubber.
ERG’s Expertise in Acid Fume Treatment
The Autosmart project illustrates how ERG brings packed tower scrubbing, liquid recirculation and air handling together for a manufacturing extraction system. For similar projects, ERG can assess the extracted airflow, the compounds present and the required treatment duty to select suitable equipment and materials.
Contact ERG Air Pollution Control to discuss sulphuric acid fume treatment or packed tower scrubbing for a new production line.